751.33 Concrete Semi Deep Abutments: Difference between revisions
No edit summary |
m →751.33.4.1 Front Elevation: Per BR, updated link |
||
(8 intermediate revisions by 2 users not shown) | |||
Line 16: | Line 16: | ||
|} | |} | ||
Modulus of elasticity, | |||
::::::<math>E_c = 33,000\ K_1 \ (w_c^{1.5}) \sqrt{f^'_c}</math> | |||
: | Where: | ||
:f'<sub>c</sub> in ksi | |||
:w<sub>c</sub> = unit weight of nonreinforced concrete = 0.145 kcf | |||
:K<sub>1</sub> = correction factor for source of aggregate | |||
::= 1.0 unless determined by physical testing | |||
Modulus of rupture, | |||
::::::<math> f_r \ = \ 0.24 \sqrt{f'_{c}}</math> LRFD 5.4.2.6 | |||
Where: | |||
:f'<sub>c</sub> is in ksi | |||
Line 98: | Line 96: | ||
'''Dead Loads''' | '''Dead Loads''' | ||
Loads from stringers/girders shall be applied as concentrated loads at the intersection of the centerline of stringer/girder and the centerline of the bearing. | Loads from stringers/girders shall be applied as concentrated loads at the intersection of the centerline of stringer/girder and the centerline of the bearing. | ||
Loads from | |||
Loads from abutment components (abutment slab, barrier or railing, wings, apron, curtain wall, etc.) shall be applied to the bearing beam and transverse approach beam respectively as uniform distributed loads for the computation of pile loads and reinforcement. | |||
Line 162: | Line 161: | ||
Use an equivalent fluid pressure of 45 pcf. | Use an equivalent fluid pressure of 45 pcf. | ||
Include a collision impact load applied to the barrier | Include a collision impact load applied to the barrier or railing transferred to the wing. | ||
Assume LL surcharge lateral load of 90 pcf. | Assume LL surcharge lateral load of 90 pcf. | ||
Line 196: | Line 195: | ||
|valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |Top of curtain wall to be 2” below the slab of the adjoining span. | |valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |Top of curtain wall to be 2” below the slab of the adjoining span. | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 2.gif]]||align="left" width="400pt" |An access door shall be used only when called for on the Design Layout Sheet. | |valign="top"|[[Image:751.33 circled 2.gif]]||align="left" width="400pt" |An access door shall be used only when called for on the Design Layout Sheet (based on utility need or removal of form need). | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 3.gif]]||align="left" width="400pt" |It may be necessary to increase Abutment Length so end of wing extends beyond the intersection of the ground line and top of slab at the outside edge of wing. | |valign="top"|[[Image:751.33 circled 3.gif]]||align="left" width="400pt" |It may be necessary to increase Abutment Length so end of wing extends beyond the intersection of the ground line and top of slab at the outside edge of wing. | ||
Line 220: | Line 219: | ||
|valign="top"|[[Image:751.33 circled 3.gif]]||align="left" width="400pt" |If length is greater than 15’-0”, Apron wall reinforcement shall be designed. | |valign="top"|[[Image:751.33 circled 3.gif]]||align="left" width="400pt" |If length is greater than 15’-0”, Apron wall reinforcement shall be designed. | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 4.gif]]||align="left" width="400pt" |Abutment Slab Depth + 1/2” ( | |valign="top"|[[Image:751.33 circled 4.gif]]||align="left" width="400pt" |Abutment Slab Depth + 1/2” (Min.) | ||
|- | |||
|valign="top"|[[Image:751.33 circled 5.gif]]||align="left" width="400pt" |12” (Min.) at gutter line to the top of the Transverse Approach Beam, except when the Abutment Slab depth is 12” or greater, then place the top of the Transverse Approach Beam 1/2” below the bottom of the slab. | |||
|- | |- | ||
|valign="top"| | |valign="top"|(*)||Provide a minimum of 8" cl. from outside edge of pile to face of beam. | ||
|} | |} | ||
Line 261: | Line 262: | ||
|valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |21” (Min.), 2’-0” (Max). | |valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |21” (Min.), 2’-0” (Max). | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 2.gif]]||align="left" width="400pt" |30” or 2.5 | |valign="top"|[[Image:751.33 circled 2.gif]]||align="left" width="400pt" |30” or 2.5 x pile diameter (Min.), 12’-0” (Max.) spacing, 1” increments. | ||
|- | |||
|valign="top"|(*)||Provide a minimum of 8" cl. from outside edge of pile to face of beam. | |||
|} | |} | ||
Line 274: | Line 277: | ||
See | See Table below for [[#reinforcement|reinforcement]] not shown. | ||
All transverse steel to be placed parallel to the backwall. All main steel to be placed parallel to the centerline of roadway. | All transverse steel to be placed parallel to the backwall. All main steel to be placed parallel to the centerline of roadway. | ||
Line 280: | Line 283: | ||
Epoxy coat all reinforcing in abutment slab, bearing beam, curtain wall, apron wall, backwall, and transverse approach beam. | Epoxy coat all reinforcing in abutment slab, bearing beam, curtain wall, apron wall, backwall, and transverse approach beam. | ||
When expansion devise is present use details of [[751. | When expansion devise is present use details of [[751.13 Expansion Joint Systems#751.13.1.4 Details of Substructure Protection|protective coating and sloping top of beam to drain]]. | ||
(*) If height of [[#Equivalent Fluid Pressure A|Equivalent Fluid Pressure A]] is greater than 5 ft. or if apron wall extends more than 15 ft. below bearing beam, reinforcement will need to be verified. | (*) If height of [[#Equivalent Fluid Pressure A|Equivalent Fluid Pressure A]] is greater than 5 ft. or if apron wall extends more than 15 ft. below bearing beam, reinforcement will need to be verified. | ||
Line 303: | Line 306: | ||
|valign="top"|[[Image:751.33 circled 5.gif]]||align="left" width="400pt" |#6 Bars at 8” cts. (Each face) | |valign="top"|[[Image:751.33 circled 5.gif]]||align="left" width="400pt" |#6 Bars at 8” cts. (Each face) | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 6.gif]]||align="left" width="400pt" | | |valign="top"|[[Image:751.33 circled 6.gif]]||align="left" width="400pt" |For details of K bars, see [[751.12 Barriers, Curbs and Fences#751.12.1.4.3 End of Barrier Reinforcement|EPG 751.12.1.4.3 End of Barrier Reinforcement]] for Type B barrier and [[751.12 Barriers, Curbs and Fences#751.12.1.3.3 End of Barrier Reinforcement|EPG 751.12.1.3.3 End of Barrier Reinforcement]] for Type D and H barriers. | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 7.gif]]||align="left" width="400pt" |If end of wing wall is greater than 5’-0” deep, reinforcement will need to be verified. | |valign="top"|[[Image:751.33 circled 7.gif]]||align="left" width="400pt" |If end of wing wall is greater than 5’-0” deep, reinforcement will need to be verified. | ||
Line 317: | Line 320: | ||
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center" | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center" | ||
|- | |- | ||
| ||align="left"|See | | ||align="left"|See Table below for [[#reinforcement|reinforcement]]. | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |2 1/2" Cl. (To clear the const. joint key). | |valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |2 1/2" Cl. (To clear the const. joint key). | ||
Line 381: | Line 384: | ||
|valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |Use 3” (min.) and 6” (max.) (Typ.). | |valign="top"|[[Image:751.33 circled 1.gif]]||align="left" width="400pt" |Use 3” (min.) and 6” (max.) (Typ.). | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 2.gif]]||align="left" width="400pt" |See [[751.33_Concrete_Semi_Deep_Abutments#751.33.4.5_Bearing_Beam| | |valign="top"|[[Image:751.33 circled 2.gif]]||align="left" width="400pt" |See [[751.33_Concrete_Semi_Deep_Abutments#751.33.4.5_Bearing_Beam|EPG 751.33.4.5]] | ||
|- | |- | ||
|valign="top"|[[Image:751.33 circled 3.gif]]||align="left" width="400pt" |Varies (12” max.) | |valign="top"|[[Image:751.33 circled 3.gif]]||align="left" width="400pt" |Varies (12” max.) | ||
Line 507: | Line 510: | ||
[[Category:751 LRFD | [[Category:751 LRFD Bridge Design Guidelines]] |
Latest revision as of 12:43, 11 January 2022
751.33.1 General
751.33.1.1 Material Properties
Concrete | ||
---|---|---|
Class B Concrete (Substructure) | = 3.0 ksi | |
= 10 ksi | ||
Class B-2 Concrete (Abutment Slab) | = 4.0 ksi | |
= 8 ksi |
Modulus of elasticity,
Where:
- f'c in ksi
- wc = unit weight of nonreinforced concrete = 0.145 kcf
- K1 = correction factor for source of aggregate
- = 1.0 unless determined by physical testing
Modulus of rupture,
- LRFD 5.4.2.6
Where:
- f'c is in ksi
Reinforcing Steel | ||
---|---|---|
Minimum yield strength, | = 60.0 ksi | |
Steel modulus of elasticity, | = 29000 ksi |
751.33.2 Design
751.33.2.1 Limit States and Factors
In general, each component shall satisfy the following equation:
Where:
= Total factored force effect | |
= Force effect | |
= Load modifier | |
= Load factor | |
= Resistance factor | |
= Nominal resistance | |
= Factored resistance |
Limit States
The following limit states shall be considered for abutment design:
- STRENGTH – I
- STRENGTH – III
- STRENGTH – IV
- STRENGTH – V
- SERVICE – I
- FATIGUE
- EXTREME EVENT - II
See LRFD Table 3.4.1-1 and LRFD 3.4.2 for Loads and Load Factors applied at each given limit state.
Resistance factors
- STRENGTH limit states, see LRFD 6.5.4.2 and LRFD 5.5.4.2
- For all other limit states, = 1.00
751.33.2.2 Distribution of Loads
Dead Loads
Loads from stringers/girders shall be applied as concentrated loads at the intersection of the centerline of stringer/girder and the centerline of the bearing.
Loads from abutment components (abutment slab, barrier or railing, wings, apron, curtain wall, etc.) shall be applied to the bearing beam and transverse approach beam respectively as uniform distributed loads for the computation of pile loads and reinforcement.
Live Loads
Loads from stringers/girders shall be applied as concentrated loads at the intersection of the centerline of stringer/girder and the centerline of the bearing. Loads from the Abutment Slab shall be applied to the Transverse Approach Beam as a uniform distributed load for the computation of pile loads and reinforcement. No Live load shall be distributed through the Abutment Slab to the Bearing Beam for computations of pile loads or reinforcement
Wind, Temperature, Frictional Loads
These loads shall be disregarded, except for special cases or if specified by the Structural Project Manager, or on the Design Layout Sheet.
Earth Pressure Loads
Earth pressure loads are applied to the apron wall and part of the wing wall that extends past the transverse approach beam respectively. All tables have these forces already incorporated. For all special designs, these forces shall be applied appropriately.
(*) Or compute using the angle, when it is given
Note: Do not use earth pressure on the front faces.
Elevation751.33.2.3 Design Assumptions
Abutment Slab
Assume a uniform 3” wearing surface load. Assume slab to be acting one-way parallel with roadway.
Bearing Beam
The beam is assumed continuous over supports at centerline of piles. Live loads are applied to the superstructure only. Live loads are not simultaneously applied to the abutment slab.
Transverse Approach Beam
The beam is assumed continuous over supports at centerline of piles. The beam is assumed to carry half of the dead load of the approach slab. Live loads are applied to the abutment slab only. Live loads are not simultaneously applied to the approach slab.
Apron Wall
Assume apron wall to be cantilevered off of bearing beam with no support from battered piles. Use an equivalent fluid pressure of 45 pcf.
Wing Wall
Assume wing wall to be cantilevered at the fill face side of the transverse approach beam.
Assume 1’-0” of soil braces wing wall bottom at short end of wall.
Use an equivalent fluid pressure of 45 pcf.
Include a collision impact load applied to the barrier or railing transferred to the wing.
Assume LL surcharge lateral load of 90 pcf.
Piles
Stresses in the piles due to bending need not be considered in design calculations, except for seismic design.
751.33.2.4 Design Process
There are many ways to go about designing a Semi-Deep Abutment. Below is one process, which will work for most standard abutments. A majority of the steps are interchangeable, and can be switched to meet the designers’ preference.
- Design geometry of abutment
- Calculate the size and number of piles required for the bearing beam
- Determine the bearing beam reinforcement
- Calculate the size and number of piles required for the transverse beam
- Determine the other abutment components reinforcement
751.33.3 Geometry
Use the standard illustrations in this section, information from your superstructure calculations, and the design layout sheet to design the geometry of the abutment.
751.33.3.1 Wing Elevation
751.33.3.2 Cross-Section
751.33.3.3 Plan View
Square Structures | Skewed Structures |
---|---|
Plan View |
751.33.3.4 Front Elevation
Slope toe of Apron Wall when the ends of the walls differ in elevations by more than 2’-0”. (or when beam is sloped) | |
Slope top of backwall when the slab haunch exceeds 6” (at gutter line). |
751.33.3.5 Pile Location
21” (Min.), 2’-0” (Max). | |
30” or 2.5 x pile diameter (Min.), 12’-0” (Max.) spacing, 1” increments. | |
(*) | Provide a minimum of 8" cl. from outside edge of pile to face of beam. |
751.33.4 Reinforcement
751.33.4.1 Front Elevation
See Table below for reinforcement not shown.
All transverse steel to be placed parallel to the backwall. All main steel to be placed parallel to the centerline of roadway.
Epoxy coat all reinforcing in abutment slab, bearing beam, curtain wall, apron wall, backwall, and transverse approach beam.
When expansion devise is present use details of protective coating and sloping top of beam to drain.
(*) If height of Equivalent Fluid Pressure A is greater than 5 ft. or if apron wall extends more than 15 ft. below bearing beam, reinforcement will need to be verified.
751.33.4.2 Wing Elevation
Varies (12” Max.) | |
#4 Bars at 12” cts. (Each face) | |
#5 Bars at 12” cts. (Each face) | |
12” (Min.) (Development length) | |
#6 Bars at 8” cts. (Each face) | |
For details of K bars, see EPG 751.12.1.4.3 End of Barrier Reinforcement for Type B barrier and EPG 751.12.1.3.3 End of Barrier Reinforcement for Type D and H barriers. | |
If end of wing wall is greater than 5’-0” deep, reinforcement will need to be verified. |
751.33.4.3 Cross-Section
See Table below for reinforcement. | |
2 1/2" Cl. (To clear the const. joint key). | |
#4 @ 12" cts. (Max). |
Abutment Slab Design Lengths (*) |
Uniform Abutment Slab Thickness |
Axle Vehicle Live Load (***) |
Abutment Slab Bottom Steel Parallel to C.L. Rdwy. |
Abutment Slab Top Steel Each Way |
Transverse Approach Beam Reinforcement (Top & Bot.) (****) | |||||
Pile Spacing | ||||||||||
7' | 8' | 9' | 10' | 11' | 12' | |||||
10'-0" | 11" | 40.00 k | #8 at 9" cts. | #4 at 18" cts. | 4-#6 | 4-#6 | 4-#6 | 4-#6 | 4-#7 | 4-#8 |
15'-0" | 12" | 43.33 k | #8 at 8" cts. | #4 at 12" cts. | 4-#6 | 4-#6 | 4-#6 | 4-#7 | 4-#7 | 4-#8 |
20'-0" | 15" | 45.00 k | #8 at 7" cts. | #4 at 12" cts. | 4-#6 | 4-#6 | 4-#7 | 4-#7 | 4-#8 | 4-#8 |
25'-0" | 17" | 46.08 k | #8 at 5" cts. | #4 at 12" cts. | 4-#6 | 4-#6 | 4-#7 | 4-#7 | 4-#8 | 6-#8 |
30'-0" | 20" | 49.60 k | #9 at 6" cts. | #5 at 12" cts. | 4-#6 | 4-#7 | 4-#7 | 4-#8 | 6-#8 | 6-#8 |
35'-0" | 22" | 52.80 k | #9 at 5" cts. | #5 at 12" cts. | 4-#6 | 4-#7 | 4-#8 | 4-#8 | 6-#8 | 6-#8 |
Transverse Approach Beam Stirrup Size | #4 | #4 | #5 | #5 | #6 | #6 |
(*) Abutment slab design length is measured from the center of the backwall to the center of the approach beam along the centerline of roadway.
(**) For abutment slabs with lengths greater than 35’-0”, an intermediate bent is required inside the semi-deep abutment. Top and bottom reinforcement for these slabs shall be designed by the designer.
(***) Use the axle vehicle live load for calculating pile loads for the transverse approach beam.
(****) 4-#9’s can be used in lieu of 6-#8’s if spacing restrictions require fewer bars.
751.33.4.4 Plan View
See table above for reinforcement not shown. | |
Use 3” (min.) and 6” (max.) (Typ.). | |
See EPG 751.33.4.5 | |
Varies (12” max.) | |
Stirrup to be centered over pile (Typ.). | |
If nominal pile capacity is greater than 110 tons, stirrup size and spacing needs to be verified. |
751.33.4.5 Bearing Beam
= | |
= Superstructure Loads (Applied through beam seat) | |
= Uniform DL (Abutment Components) | |
= Pile Spacing (ft.) |
Min. Reinforcement: | |
Crack Control Parameters: | |
See LRFD 5.7.3.4 for variable definitions.
751.33.4.6 Pile Haunches
751.33.5 Details
751.33.5.1 Front Sheet
Figure shown below is an example of the information to be included on the abutment plan view on the first sheet of the plans.
Details for unsymmetrical roadways will require dimensions tying centerline of roadway to centerline of structure. (Pile coordinates shall be to centerline of roadway)
751.33.5.2 Ground line within Abutments
Figure shown below shall be detailed on the first or second sheet of the plans.
751.33.5.3 Construction Joints
(*) When the total length of beam and backwall exceeds 60'-0", use keyed construction joint at or near centerline Abutment as shown, perferably located at a 1/4 point between piles
751.33.5.4 Access Door
- Cost of the door is to be included in other items.
- Cut or bend reinforcing steel in the field to clear the opening for the access door.