751.35 Concrete Pile Cap Integral End Bents: Difference between revisions

From Engineering_Policy_Guide
Jump to navigation Jump to search
Smithk (talk | contribs)
m Per BR, clarified #5-H (L shaped) approach slab anchorage bars, end of slab, and fill face of end bent. Revised lap splice for U and V bars in end bents.
 
(30 intermediate revisions by 3 users not shown)
Line 96: Line 96:
'''Dead Loads'''
'''Dead Loads'''


Loads from stringers, girders, etc. shall be applied as concentrated loads applied at the centerline of bearing.  Loads from concrete slab spans shall be applied as uniformly distributed loads.
Loads from beams, girders, etc. shall be applied as concentrated loads applied at the centerline of bearing.  Loads from concrete slab spans shall be applied as uniformly distributed loads.




'''Live Loads'''
'''Live Loads'''


Loads from stringers, girders, etc. shall be applied as concentrated loads applied at the centerline of bearing.  Dynamic load allowance (impact) should be included for the design of the beam.  No dynamic load allowance should be included for foundation design.
Loads from beams, girders, etc. shall be applied as concentrated loads applied at the centerline of bearing.  Dynamic load allowance (impact) should be included for the design of the beam.  No dynamic load allowance should be included for foundation design.
 
For wings with detached wing walls, no portion of the bridge live load shall be distributed to the detached wall.  The detached wing wall shall be designed as a [[751.24_Retaining_Walls|retaining wall]].  The weight of the safety barrier curb on top of the wall shall be included in the dead load.


For wings with detached wing walls, no portion of the bridge live load shall be distributed to the detached wall.  The detached wing wall shall be designed as a [[751.24 LFD Retaining Walls|retaining wall]].  The weight of the barrier or railing on top of the wall shall be included in the dead load.


'''Collision'''
'''Collision'''
Line 138: Line 137:
The following steps shall be used to design integral end bents.
The following steps shall be used to design integral end bents.


====751.35.2.4.1 Beam Cap Design====


'''Step 1 – Obtain loads from superstructure'''
'''Step 1 – Obtain loads from superstructure'''
Line 179: Line 179:
The minimum reinforcement and bar spacing shall also be checked against the appropriate limits.
The minimum reinforcement and bar spacing shall also be checked against the appropriate limits.


====751.35.2.4.2 Pile Design====
Follow Fig. 751.35.2.4.2 Integral Abutment Pile Design Flowchart and select applicable pile design method from following list:
:1. Rigorous pile design procedure
:2. Simple pile design procedure
:3. Design pile in accordance with LRFD specification
[[Image:751.35.2.4.2.jpg|center|800px]]
<center>'''Fig. 751.35.2.4.2 Integral Abutment Pile Design Flowchart'''</center>
=====751.35.2.4.2.1  Rigorous Pile Design Procedure=====
See Development Section, Structural Project Manager (SPM), or Structural Liaison Engineer (SLE), or [[media:751.35.2.4.2.1.pdf|17-01-SEP-New Integral End Bent Pile Design Procedure]].
=====751.35.2.4.2.2 Simple Pile Design Procedure=====
Use this procedure if bridge meets the length and skew limits tabulized in Fig. 751.35.2.4.2, Integral Abutment Pile Design Flowchart, bridge does not require a complete seismic analysis and where scour can be ignored.
Simple curved structures following similar length and skew limits are allowed. Complex thermal movements may require rigorous procedure.
Minimum pile embedment, See [[751.1 Preliminary Design#751.1.2.22 Types of Piling|EPG 751.1.2.22 Types of Piling]].
Rotate HP piles for skews over 45°, resulting in strong axis parallel to center line of beam cap.
Show pile prebore elevation on the plan where applicable in accordance with flowchart.  Side friction in prebored areas shall be ignored.


'''Step 5 – [[751.36_Driven_Piles|Design for number and size of pile]]'''
See [[751.36 Driven Piles#751.36.5.7.1 Integral End Bent Simple Pile Design|EPG 751.36.5.7.1  Integral End Bent Simple Pile Design]] for typical pile design values.


=== 751.35.2.5 Beam Reinforcement Special Cases ===
=== 751.35.2.5 Beam Reinforcement Special Cases ===
Line 245: Line 270:
=== 751.35.3.3 Prestressed Girder End Bent ===
=== 751.35.3.3 Prestressed Girder End Bent ===


{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
[[image:751.35.3.3.1.jpg|750px|center]]
|-
|[[Image:751.35.3.3.jpg|850px]]
|-
!width="50%"|Section Near Wing||Section A-A
|}
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|valign="top" align="right"|[[Image:751.35 circled 1.gif]]||align="left" width="400pt" |12" minimum at gutter line at end of slab.
|-
|valign="top" align="right"|[[Image:751.35 circled 2.gif]]||align="left" width="400pt" |All concrete in the end bent above top of beam and below top of slab shall be class B-2.
|-
|valign="top" align="right"|[[Image:751.35 circled 3.gif]]||align="left" width="400pt" |Provide a minimum of 8" cl. from outside edge of pile to face of beam. For pile greater than 14” wide (dia.), shifting pile centerline towards fill face is preferred based on structural considerations (eccentric load to pile). Otherwise, increase abutment beam width (1” increments) towards front face in order to meet 8” min. cl.


Example:
:::(1) See [[751.12 Barriers, Railings, Curbs and Fences|EPG 751.12 Barriers, Railings, Curbs and Fences]] for barrier or railing details.
:::(2) Keep 1 1/2" minimum clear cover for reinforcement between approach notch and girder. Increase beam width (1" increments) to get the 1 1/2" clear cover if necessary.
:::(3) Use 1” plus half of bearing pad length when bearing pads are used. Use 3 ½” minimum for NU Standard Girders and 5” minimum for MoDOT Standard Girders when girder chairs are used.
:::(4) 12" minimum at gutter line at end of slab.
:::(5) All concrete in the end bent above top of beam and below top of slab shall be Class B-2.
:::(6) Provide a minimum of 8" clearance from outside edge of pile to face of beam. For pile greater than 14” wide (diameter), shifting pile centerline towards fill face is preferred based on structural considerations (eccentric load to pile). Otherwise, increase beam width (1” increments) toward front face in order to meet 8” minimum clearance.
::::Example:  
::::Pile size = 16”
::::Option I (preferred): Shift pile centerline 1” toward fill face and consider eccentric load to the pile.
:::::Minimum beam width = 20”+16”=3’-0”
::::Option II: Increase beam width 1” toward front face.
:::::Minimum beam width = 21”+16”=3’-1”
:::(7) See Design Layout for maximum spill slope.


Pile size = 16”
Option I (preferred): Shift pile centerline 1” towards fill face and consider eccentric load to the pile.


:Min. abutment width = 20”+16”=3’-0”
[[image:751.35.3.3.2.jpg|750px|center]]
 
[[image:751.35.3.3.3.jpg|750px|center]]
Option II: Increase beam width 1” towards front face.
[[image:751.35.3.3.4.jpg|750px|center]]
 
:Min. abutment width = 21”+16”=3’-1”


{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 4.gif]]||align="left" width="400pt" |See Design Layout for maximum slope of spill fill.
|valign="top" align="right"|Note:||align="left" width="800pt" |Neoprene bearing pads are to be used on integral bents (prestressed structures) if pad size and beam clearance permit; otherwise, use girder chairs. See [[751.11 Bearings#751.11.3.6 Girder/Beam Chairs|EPG 751.11.3.6 Girder/Beam Chairs]] for additional girder chair details.
|-
|-
|valign="top" align="right"|*||align="left" width="400pt" |Keep 1 1/2" Min. clear cover for a #6 bar reinforcement between approach notch and girderIncrease abutment beam width (1" increments) to get the 1 1/2" clear cover if necessary.
| ||align="left"|Squared beam steps are shown. Steps may be skewed to facilitate placement of U1 and V1 stirrup barsSee [[#751.35.4 Reinforcement |EPG 751.35.4 Reinforcement]] for details.
|-
|-
|valign="top" align="right"|**||align="left" width="400pt" |See [[751.12_Protective_Barricades|EPG 751.12 Protective Barricades]] for barrier curb details.
|valign="top" align="right"|*||align="left" width="800pt" |18" minimum, 2'-0" maximum; provide a minimum of 8" clearance from outside edge of pile to outside face of beam.
|}
|}


=== 751.35.3.4 Steel Girder or Beam End Bent ===


{|align="center"
[[image:751.35.3.4.1.jpg|750px|center]]
|-
|colspan="2"|[[Image:751.35.3.3 keyed.jpg|350px]]
|-
!width="35%"|Detail of Keyed<br/>Const. Jt.|| &nbsp;
|}


:::(1) See [[751.12 Barriers, Railings, Curbs and Fences|EPG 751.12 Barriers, Railings, Curbs and Fences]] for barrier or railing details.
:::(2) Keep 1 1/2" minimum clear cover for reinforcement between approach notch and girder. Increase abutment beam width (1" increments) to get the 1 1/2" clear cover if necessary.
:::(3) Use 1" plus half of bearing pad length when bearing pads are used. Use 3" minimum when girder chairs are used.
:::(4) 12" minimum at gutter line at end of slab.
:::(5) All concrete in the end bent above top of beam and below top of slab shall be Class B-2.
:::(6) Provide a minimum of 8" clearance from outside edge of pile to face of beam. For pile greater than 14” wide (diameter), shifting pile centerline toward fill face is preferred based on structural considerations (eccentric load to pile). Otherwise, increase beam width (1” increments) toward front face in order to meet 8” minimum clearance.
::::Example:
::::Pile size = 16”
::::Option I (preferred): Shift pile centerline 1” toward fill face and consider eccentric load to the pile.
:::::Minimum beam width = 20”+16”=3’-0”
::::Option II: Increase beam width 1” toward front face.
:::::Minimum beam width = 21”+16”=3’-1”
:::(7) See Design Layout for maximum spill slope.


[[image:751.35.3.4.2.jpg|750px|center]]
[[image:751.35.3.4.3.jpg|750px|center]]
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|-
|[[Image:751.35.3.3 elevation.jpg|750px]]
|valign="top" align="right"|Note:||align="left" width="800pt" |Neoprene bearing pads are to be used on integral bents (steel structures) if pad size and beam clearance permit; otherwise, use girder chairs. See [[751.11 Bearings#751.11.3.6 Girder/Beam Chairs|EPG 751.11.3.6 Girder/Beam Chairs]] for additional girder chair details.
|-
|-
!Elevation
| ||align="left"|Squared beam steps are shown.  Steps may be skewed to facilitate placement of U1 and V1 stirrup bars  See [[#751.35.4 Reinforcement |EPG 751.35.4 Reinforcement]] for details.
|-
| &nbsp;
|-
|[[Image:751.35.3.3 plan squared.jpg|800px]]
|-
!Plan (Squared)
|-
| &nbsp;
|-
|-
|[[Image:751.35.3.3 plan skewed.jpg|800px]]
|valign="top" align="right"|*||align="left" width="800pt" |18" minimum, 2'-0" maximum; provide a minimum of 8" clearance from outside edge of pile to outside face of beam.
|-
|-
!Plan (Skewed)
|valign="top" align="right"|**||align="left" width="400pt" |3" minimum clearance between sole plate and keyed construction joint (typical)
|}
|}


{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
=== 751.35.3.5 Wing and Detached Wing Walls ===
|-
 
|valign="top" align="right"|Note:||align="left" width="400pt" |Neoprene bearing pads are to be used on integral bents (steel or prestressed structures) if pad size and beam clearance permit; otherwise, use girder chairs.
For seismic design category A: When wing length, L, is greater than 22’-0”, use  maximum 22’-0” integral abutment wing wall combined with detached wing wall.
|-
| ||align="left"|Squared beam steps are shown. Steps may be skewed to facilitate placement of U1 and V1 stirrup bars.  See [[#751.35.4 Reinforcement |EPG 751.35.4 Reinforcement]] for details.
|-
|valign="top" align="right"|*||align="left" width="400pt" |18" (min.) 2'-0" (max.); provide a minimum of 8" cl. from outside edge of pile to outside face of beam.
|}


=== 751.35.3.4 Steel Girder or Beam End Bent ===
Standard wing reinforcement is developed assuming a pinned connection at the bottom (tip) of wing. This assumption is applicable for cases where the passive pressure from the fill slope can be counted on to partially resist the active forces from the backfill. In a seismic event the forces on the wings are developed by the wings moving into the soil backfill and the fill slope resistance is less reliable. For seismic forces wings shall be designed assuming there is no lateral restraint at the bottom of the wing. The reduced restraint conditions require a more practical limit for the wing length.


{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
<gallery mode=packed widths=200px heights=200px>
|-
File:751.35.3.5-01.jpg|
|[[Image:751.35.3.4.jpg|850px]]
File:751.35.3.5-02.jpg|
|-
</gallery>
!width="50%"|Section Near Wing||Section A-A
<center>
|}
<gallery mode=nolines perrow=1 widths=550 heights=550px>
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
File:751.35.3.5-03.jpg| <big>'''Section A-A'''</big>
|-
File:751.35.3.5-04.jpg| <big>'''Detail B'''</big>
|valign="top" align="right"|[[Image:751.35 circled 1.gif]]||align="left" width="400pt" |12" minimum at gutter line at end of slab.
</gallery>
|-
</center>
|valign="top" align="right"|[[Image:751.35 circled 2.gif]]||align="left" width="400pt" |All concrete in the end bent above top of beam and below top of slab shall be class B-2.
{|border="0" cellpadding="5" cellspacing="1" align="center" valign="top"
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 3.gif]]||align="left" width="400pt" |Provide a minimum of 8" cl. from outside edge of pile to face of beam. For pile greater than 14” wide (dia.), shifting pile centerline towards fill face is preferred based on structural considerations (eccentric load to pile). Otherwise, increase abutment beam width (1” increments) towards front face in order to meet 8” min. cl.
| Note: || width="650" |
 
Example:
 
Pile size = 16”
 
Option I (preferred): Shift pile centerline 1” towards fill face and consider eccentric load to the pile.
 
:Min. abutment width = 20”+16”=3’-0”
 
Option II: Increase beam width 1” towards front face.
 
:Min. abutment width = 21”+16”=3’-1”
 
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 4.gif]]||align="left" width="400pt" |See Design Layout for maximum slope of spill fill.
| valign="top" | '''*''' || width="650" | Detached wing wall shown is for illustration purpose only. Design detached wing wall as a [[751.24_Retaining_Walls|retaining wall (EPG 751.24)]].
|-
|-
|valign="top" align="right"|*||align="left" width="400pt" |Use 3" Min. when girder chairs are used and use 1" past the end of the bearing pad when bearing pads are used.
| valign="top" | '''**''' || Use retaining wall design.
|-
|-
|valign="top" align="right"|**||align="left" width="400pt" |Keep 1 1/2" min. clear cover for a #6 bar reinf. between approach notch and girder.  Increase abutment beam width (1" increments) to get the 1 1/2" clear cover if necessary.
| || <sup>1</sup> For seismic design category B, C and D only: The wing length shall not be greater than 17 feet. When a detached wing wall is required the integral abutment wing length shall not exceed 17 feet.
|-
|-
|valign="top" align="right"|***||align="left" width="400pt" |See [[751.12_Protective_Barricades|EPG 751.12 Protective Barricades]] for barrier curb details.
| || Report Pile Cut-off Elevation and Minimum Galvanized Penetration (Elev.) (See [[751.50_Standard_Detailing_Notes#E2._Foundation_Data_Table|EPG 751.50 Standard Detailing Note E2, (Foundation Data Table)]].
|}
|}


== 751.35.4 Reinforcement ==


{|align="center"
For epoxy coated reinforcement requirements, see [[751.5 Structural Detailing Guidelines#751.5.9.2.2 Epoxy Coated Reinforcement Requirements|EPG 751.5.9.2.2 Epoxy Coated Reinforcement Requirements]].
|-
|colspan="2"|[[Image:751.35.3.4 keyed.jpg|350px]]
|-
!width="35%"|Detail of Keyed<br/>Const. Jt.|| &nbsp;
|}
 


{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
=== 751.35.4.1 Wide Flange Beams & Plate Girders ===
|-
<center>
|[[Image:751.35.3.4 elevation.jpg|800px]]
{|border="0" cellpadding="5" cellspacing="1" style="text-align:left"
|-
|-
!Elevation
|colspan="4"|[[Image:751.35.4.1.1 2020.jpg|750px]]
|-
|-
| &nbsp;
|colspan="4"|[[Image:751.35.4.1.2 2020.jpg|800px]]
|-
|-
|[[Image:751.35.3.4 plan squared.jpg|800px]]
|rowspan="22" valign="center"|[[Image:751.35.4-03-2024.png|225px]]||colspan="3"|'''Detailing Guidance:'''
|-
|-
!Plan (Squared)
|width="15px" rowspan="19"|<font color = "white">ko</font color = "white">  ||colspan="2"|<font color = "green">Green items</font color = "green"> are guidance only and shall not be shown plans.
|-
|-
| &nbsp;
|colspan="2"|Place all U bars and V pairs parallel to centerline roadway.
|-
|-
|[[Image:751.35.3.4 plan skewed.jpg|800px]]
|colspan="2"|Keep 1 1/2" clearance between the piles and the U1 or U2 bars.  
|-
|-
!Plan (Skewed)
|colspan="2"|Keep 1 1/2" clearance between the beams or girders and the U1 or V1 bars.
|}
 
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|-
|valign="top" align="right"|Note:||align="left" width="400pt" |Neoprene bearing pads are to be used on integral bents (steel or prestressed structures) if pad size and beam clearance permit; otherwise, use girder chairs.
|colspan="2"|Keep 1 1/2" clearance between the angles of girder chairs and the U2 or U3 bars.  
|-
|-
| ||align="left"|Squared beam steps are shown.  Steps may be skewed to facilitate placement of U1 and V1 stirrup bars See [[#751.35.4 Reinforcement |EPG 751.35.4 Reinforcement]] for details.
|colspan="2"|Replace U1 bars with U3 bars at piles under beams or girders.  
|-
|-
|valign="top" align="right"|*||align="left" width="400pt" |18" (min.) 2'-0" (max.); provide a minimum of 8" cl. from outside edge of pile to outside face of beam.
|colspan="2"|Replace U1 bars with V1 bars at piles between beams or girders.  
|-
|-
|valign="top" align="right"|**||align="left" width="400pt" |3" cl. between sole plate and keyed const. joint (typ.)
|colspan="2"|When dimension “A” is required to be greater than 15” to clear piles by 1 ½”, typical when HP14 and CIP14 or larger diameter piles are used, add intermediate longitudinal bar(s) between piles. The spacing between intermediate bar(s) and full length bars shall not be greater than required by crack control provisions. Ends of intermediate bar(s) shall be hooked.  
|}
 
=== 751.35.3.5 Wing & Detached Wing Walls ===
 
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|-
|colspan="2"|[[Image:751.35.3.5.jpg|300px]]
|colspan="2"|See [https://epg.modot.org/index.php/751.50_Standard_Detailing_Notes#G1._Concrete_Bents EPG 751.50 G1 Concrete Bents] for appropriate notes to be placed with details.
|-
|-
|colspan="2"| &nbsp;
|valign="top" width="30"|<font color = "green">(1)</font color = "green"> ||#6-U bar ([[Image:751.35 wide flange and plate girders--6-u-bar.gif]]) at 9" centers between barrier curbs. For shallow beams where 26” is not available extend to top of beam minus 1” clear.
|-
|-
|colspan="2"|[[Image:751.35.3.5 detached wing.jpg|350px]]
|valign="top"|<font color = "green">(2)</font color = "green"> ||U4 bars ([[Image:751.35 wide flange and plate girders--5-u4-bar.gif|13px]]) and #6-U5 bars ([[Image:751.35 wide flange and plate girders--6-u-bar.gif]]) spliced with U1 ([[Image:751.35 wide flange and plate girders-u1-bar.gif]]) and V1 bars (│). U4 bars shall be same size as U1 bars. Show lap splice on plans as shown. For shallow beams stirrup hooks may be required for U4 bars ( [[image:751.35 shape37S-2024.png|14px]] -Shape 37S) (see Alternate Sections). For shallow beams where 16” is not available extend stirrup hooks to top of beam minus 1” clear.
|-
|-
|colspan="2"| &nbsp;
|valign="top"|<font color = "green">(3)</font color = "green"> ||U1 bars ([[Image:751.35 wide flange and plate girders-u1-bar.gif]]) at 12" centers. Typically #5 bars, except [https://epg.modot.org/index.php/751.35_Concrete_Pile_Cap_Integral_End_Bents#751.35.2.5_Beam_Reinforcement_Special_Cases special cases]. Replace with pairs of #5-V1 bars (│) at piles. Make sure U1 and V1 bars extend enough to meet lap length requirement across length of diaphragm. For shallow beams stirrup hooks may be required for U1 bars ( [[image:751.35 shape37S-2024.png|14px]] -Shape 37S) and end hooks may be required for V1 bars ([[image:751.35.4.1 V1 hook.jpg|8px]]) (see alternate sections). For shallow beams where 16” is not available extend hooks to approach notch minus 1 1/2" clear.
|-
|-
|[[Image:751.35.3.5 section a-a.jpg|800px]]
|valign="top"|<font color = "green">(4)</font color = "green"> ||Stirrups shall clear step by 1 1/2" minimum, if not lengthen step or skew step.
|-
|-
!Section A-A||Detail "C"
|valign="top"|<font color = "green">(5)</font color = "green"> ||#6-V bars at no more than 9” centers at the end of girders or beams.
|-
|-
|colspan="2"| &nbsp;
|valign="top"|<font color = "green">(6)</font color = "green"> ||#5-U bars (15”H x 24”V) @ about 12" centers placed parallel to centerline roadway. When approach slab haunch is expected to be greater than 18” at the roadway crown at the end of slab, slope the approach slab notch providing 12” of constant approach slab haunch or with SPM or SLE approval greater than 18” approach slab haunch may be used but increase vertical leg length of #5-U bars to ensure 12” minimum embedment.<br/>For shallow beams where 12” embedment is not available adjust length of vertical leg and extend to top of beam minus 1” clear.
|-
|-
|[[Image:751.35.3.5 section d-d.jpg|850px]]
|valign="top"|<font color = "green">(7)</font color = "green"> ||With SPM or SLE approval a 29” splice may be used in combination with specifying 2” cover to U bars and V bars if doing so avoids the need for using hooked bars.
|-
|-
!Detail B||Section D-D
|valign="top"|<font color = "green">(8)</font color = "green">||See [https://epg.modot.org/index.php/751.35_Concrete_Pile_Cap_Integral_End_Bents#web_hole_tabel tables] for 1 1/16" round hole spacing for #6-H bars.
|}
 
{|border="0" cellpadding="5" cellspacing="1" align="center"
|-
|-
|align="right" valign="top"|*||width="400pt"|Detached wing wall shown is for illustration purpose only.  Design detached wing wall as a [[751.24 LFD Retaining Walls|LFD retaining wall (EPG 751.24)]].
|valign="top"|<font color = "green">(9)</font color = "green"> ||Same number of bars as 1 1/16" round holes in beam or girder.
|-
|-
|align="right" valing="top"|**||width="400pt"|See [[751.24 LFD Retaining Walls|EPG 751.24 LFD Retaining Walls]].
|valign="top"|<font color = "green">(10)</font color = "green"> || Add intermediate longitudinal bar(s) when required for spacing. Keep 3” minimum clearance between the pile and intermediate longitudinal bar(s).
|}
|}
</center>
[[Image:751.35.4-04-2024.png|center|800px]]


== 751.35.4 Reinforcement ==
=== 751.35.4.2 Prestressed I-Girders, Bulb-Tee Girders and NU-Girders ===


 
<center>
=== 751.35.4.1 Wide Flange Beams & Plate Girders ===
{|border="0" cellpadding="5" cellspacing="1" style="text-align:left"
 
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|colspan="3"|[[Image:751.35.4.1 2016.jpg|900px]]
|-
!colspan="3"|Part Section Near End Bent
|-
|[[Image:751.35.4.1 sections.jpg|900px]]
|-
!Section A-A||Section B-B||Section C-C
|-
|[[Image:751.35.4.1 section d-d.jpg|225px]]
|rowspan="5" colspan="2"|
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|&nbsp;||align="left" width="400pt" |Place all U bars and V pairs parallel to centerline roadway.
|-
|valign="top" align="right"|[[Image:751.35 circled 1.gif]]||align="left" width="400pt" |#6 U-bar [[Image:751.35 wide flange and plate girders--6-u-bar.gif]] at 9" centers between barrier curbs.
|-
|valign="top" align="right"|[[Image:751.35 circled 2.gif]]||align="left" width="400pt" |U4 bars [[Image:751.35 wide flange and plate girders--5-u4-bar.gif|13px]] and #6-U5 bars [[Image:751.35 wide flange and plate girders--6-u-bar.gif]] spliced with U1 and V1 bars.  U4 bars shall be same size as U1 bars. Show lap length on plans as shown here.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 3.gif]]||align="left" width="400pt" |U1 bars [[Image:751.35 wide flange and plate girders-u1-bar.gif]] at 12" centers. #5 bars, except [[751.35_Concrete_Pile_Cap_Integral_End_Bents#751.35.2.5_Beam_Reinforcement_Special_Cases|special cases]].  Replace with pairs of #5-V1 bars at piles. Make sure U1 and V1 bars extend enough to meet lap length requirement across backwall length.
|colspan="4"|[[Image:751.35.4.2.1.jpg|800px]]
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 4.gif]]||align="left" width="400pt" |Stirrups shall clear step by 1 1/2" min., if not lengthen step or skew step.  
|colspan="4"|[[Image:751.35.4.2.2 2020.jpg|800px]]
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 5.gif]]||align="left" width="400pt" |#6-V-bars at no more than 9” centers at the end of girders or beams.
|rowspan="21" valign="center"|[[Image:751.35.4.2-03-2024.png|225px]]||colspan="3"|'''Detailing Guidance:'''
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 6.gif]]||align="left" width="400pt" |#5-H-bars (15”H x 24”V) @ about 12" centers placed parallel to centerline roadway. When approach slab haunch is expected to be greater than 18” at the roadway crown at the end of slab, slope the approach slab notch providing 12” of constant approach slab haunch or with SPM or SLE approval greater than 18” approach slab haunch may be used but increase vertical leg length of #5-H bars to ensure 12” minimum embedment.
|width="15px" rowspan="17"|<font color = "white">ko</font color = "white">  ||colspan="2"|<font color = "green">Green items</font color = "green"> are guidance only and shall not be shown on plans.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 7.gif]]||align="left" width="400pt" | See [[#web hole tabel|tables]] for 1 1/16" round hole spacing for #6-H bars.
|colspan="2"|Place all U bars and V pairs parallel to centerline roadway.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 8.gif]]||align="left" width="400pt" |Same number of bars as 1 1/16" round holes in beam or girder.
|colspan="2"|Keep 1 1/2" clearance between the piles and the U1 or U2 bars.  
|}
|-
|-
!Section D-D
|colspan="2"|Keep 1 1/2" clearance between the beams or girders and the U1 or V1 bars.
|-
|-
|&nbsp;
|colspan="2"|Keep 1 1/2" clearance between the angles of girder chairs and the U2 or U3 bars.  
|-
|&nbsp;
|-
|&nbsp;
|}
 
Instructions:
:Keep 1 1/2" clearance between the piles and the U1 or U2 bars.
 
:Keep 1 1/2" clearance between the beams or girders and the U1 or V1 bars.
 
:Keep 1 1/2" clearance between the angles of beam/girder chairs and the U2 or U3 bars.  
 
:Replace U1 bars with U3 bars at piles under beams or girders.
 
:Replace U1 bars with V1 bars at piles between beams or girders.
 
:See [http://epg.modot.org/index.php?title=751.50_Standard_Detailing_Notes#G1._Concrete_Bents EPG 751.50 G1 Concrete Bents] for appropriate notes to be placed with details.
 
=== 751.35.4.2 Prestressed I-Girders, Bulb-Tee Girders and NU-Girders ===
 
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|-
|colspan="3"|[[Image:751.35.4.2 2016.jpg|700px]]
|colspan="2"|Replace U1 bars with U3 bars at piles under beams or girders.  
|-
|-
!colspan="3"|Part Section Near End Bent
|colspan="2"|Replace U1 bars with V1 bars at piles between beams or girders.
|-
|-
|[[Image:751.35.4.2 sections.jpg|900px]]
|colspan="2"|When dimension “A” is required to be greater than 15” to clear piles by 1 ½”, typical when HP14 and CIP14 or larger diameter piles are used, add intermediate longitudinal bar(s) between piles. The spacing between intermediate bar(s) and full length bars shall not be greater than required by crack control provisions. Ends of intermediate bar(s) shall be hooked.
|-
|-
!Section A-A||Section B-B||Section C-C
|colspan="2"|See [https://epg.modot.org/index.php/751.50_Standard_Detailing_Notes#G1._Concrete_Bents EPG 751.50 G1 Concrete Bents] for appropriate notes to be placed with details.
|-
|-
|[[Image:751.35.4.2 section d-d.jpg|225px]]
|valign="top"|<font color = "green">(1)</font color = "green"> ||#6-U bar ([[Image:751.35 wide flange and plate girders--6-u-bar.gif]]) at 9" centers between barrier curbs. For shallow beams where 26” is not available extend to top of beam minus 1” clear.
|rowspan="5" colspan="2"|
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|&nbsp;||align="left" width="400pt" |Place all U bars and V pairs parallel to centerline roadway.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 1.gif]]||align="left" width="400pt" |#6 U-bar [[Image:751.35 wide flange and plate girders--6-u-bar.gif]] at 9" centers between barrier curbs.
|valign="top"|<font color = "green">(2)</font color = "green"> ||U4 bars ([[Image:751.35 wide flange and plate girders--5-u4-bar.gif|13px]]) and #6-U5 bars ([[Image:751.35 wide flange and plate girders--6-u-bar.gif]]) spliced with U1 ([[Image:751.35 wide flange and plate girders-u1-bar.gif]]) and V1 bars (│). U4 bars shall be same size as U1 bars. Show lap splice on plans as shown. For shallow beams stirrup hooks may be required for U4 bars ( [[image:751.35 shape37S-2024.png|14px]] -Shape 37S) (see Alternate Sections). For shallow beams where 16” is not available extend stirrup hooks to top of beam minus 1” clear.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 2.gif]]||align="left" width="400pt" |U4 bars [[Image:751.35 wide flange and plate girders--5-u4-bar.gif|13px]] and #6-U5 bars [[Image:751.35 wide flange and plate girders--6-u-bar.gif]] spliced with U1 and V1 bars. U4 bars shall be same size as U1 bars. Show lap length on plans as shown here.  
|valign="top"|<font color = "green">(3)</font color = "green"> ||U1 bars ([[Image:751.35 wide flange and plate girders-u1-bar.gif]]) at 12" centers. Typically #5 bars, except [https://epg.modot.org/index.php/751.35_Concrete_Pile_Cap_Integral_End_Bents#751.35.2.5_Beam_Reinforcement_Special_Cases special cases]. Replace with pairs of #5-V1 bars (│) at piles. Make sure U1 and V1 bars extend enough to meet lap length requirement across length of diaphragm. For shallow beams stirrup hooks may be required for U1 bars ( [[image:751.35 shape37S-2024.png|14px]] -Shape 37S) and end hooks may be required for V1 bars ([[image:751.35.4.1 V1 hook.jpg|8px]]) (see alternate sections). For shallow beams where 16” is not available extend hooks to approach notch minus 1 1/2" clear.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 3.gif]]||align="left" width="400pt" |U1 bars [[Image:751.35 wide flange and plate girders-u1-bar.gif]] at 12" centers. #5 bars, except [[751.35_Concrete_Pile_Cap_Integral_End_Bents#751.35.2.5_Beam_Reinforcement_Special_Cases|special cases]]. Replace with pairs of #5-V1 bars at piles. Make sure U1 and V1 bars extend enough to meet lap length requirement across backwall length.  
|valign="top"|<font color = "green">(4)</font color = "green"> ||Stirrups shall clear step by 1 1/2" minimum, if not lengthen step or skew step.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 4.gif]]||align="left" width="400pt" |Stirrups shall clear step by 1 1/2" min.; if not, lengthen step or skew step.  
|valign="top"|<font color = "green">(5)</font color = "green"> ||#6-V bars at no more than 9” centers at the end of girders or beams.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 5.gif]]||align="left" width="400pt" |#6-V-bars at no more than 9” centers at the end of girders or beams.
|valign="top"|<font color = "green">(6)</font color = "green"> ||#5-U bars (15”H x 24”V) @ about 12" centers placed parallel to centerline roadway. When approach slab haunch is expected to be greater than 18” at the roadway crown at the end of slab, slope the approach slab notch providing 12” of constant approach slab haunch or with SPM or SLE approval greater than 18” approach slab haunch may be used but increase vertical leg length of #5-U bars to ensure 12” minimum embedment.<br/>For shallow beams where 12” embedment is not available adjust length of vertical leg and extend to top of beam minus 1” clear.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 6.gif]]||align="left" width="400pt" |#5-H-bars (15”H x 24”V) @ about 12" centers placed parallel to centerline roadway. When approach slab haunch is expected to be greater than 18” at the roadway crown at the end of slab, slope the approach slab notch providing 12” of constant approach slab haunch or with SPM or SLE approval greater than 18” approach slab haunch may be used but increase vertical leg length of #5-H bars to ensure 12” minimum embedment.
|valign="top"|<font color = "green">(7)</font color = "green"> ||With SPM or SLE approval a 29” splice may be used in combination with specifying 2” cover to U bars and V bars if doing so avoids the need for using hooked bars.
|}
|-
|-
!Section D-D
|valign="top"|<font color = "green">(8)</font color = "green"> ||Add intermediate longitudinal bar(s) when required for spacing. Keep 3” minimum clearance between the pile and intermediate longitudinal bar(s).
|}
|}
</center>
[[Image:751.35.4.2-04-2024.png|center|800px]]


Instructions:
=== 751.35.4.3 Wing Reinforcement ===


:Keep 1 1/2" clearance between the piles and the U1 or U2 bars.  
[[image:751.35.4.3.1 2020.jpg|center|800px]]
[[image:751.35.4.3.2.jpg|center|800px]]


:Keep 1 1/2" clearance between the girders and the U1 or V1 bars.  
::'''Detailing Guidance: '''
::<font color = "green">Green items</font color = "green"> are guidance only and shall not be shown on plans.
::Bar marks shown are for these details only. Vary as needed.
::K bars not shown in the Elevation of Wing for clarity. For details of K bars, see [[751.12 Barriers, Railings, Curbs and Fences#751.12.1.4.3 End of Barrier Reinforcement|EPG 751.12.1.4.3 End of Barrier Reinforcement]] for Type B barrier and [[751.12 Barriers, Railings, Curbs and Fences#751.12.1.3.3 End of Barrier Reinforcement|EPG 751.12.1.3.3 End of Barrier Reinforcement]] for Type D and H barriers.
::See [[#751.35.3.3 Prestressed Girder End Bent|EPG 751.35.3.3]] for chamfer detail.
:::<font color = "green">(a)</font color = "green"> Use dimension that provides a minimum of 3" center to center spacing between #6 bars placed horizontally and #8 bars placed with grade. See SPM or SLE if spacing at one end exceeds 8 inches due to grade.
:::<font color = "green">(b)</font color = "green"> Use construction joint on steel structures only.
:::<font color = "green">(c)</font color = "green"> 6 3/8” min and 11 3/8” max. If unable to get dimension to fall within this range using 8-inch centers, then use 6 3/8” and use “@ abt. 8” cts.”
<div id="(d)"></div>
:::<font color = "green">(d)</font color = "green"> Use 66.5” for obtuse corner of bents skewed 55 degrees or greater.
:::<font color = "green">(e)</font color = "green"> Use 54.5” for obtuse corner of bents skewed 55 degrees or greater.
:::<font color = "green">(f)</font color = "green"> See [https://epg.modot.org/index.php?title=751.50_Standard_Detailing_Notes#G1._Concrete_Bents EPG 751.50 G1 Concrete Bents] for note required for the #6-F bars.
:::<font color = "green">(g)</font color = "green"> Use 90 degree standard hook in seismic areas.
 
===751.35.4.4 Skewed Bents===
Prestressed I-girders shown in the following details, steel structures are similar.


:Keep 1 1/2" clearance between the angles of girder chairs and the U2 or U3 bars.  
The sections thru integral end bents previously shown shall be adjusted for skew as shown.  


:Replace U1 bars with U3 bars at piles under the girders.  
[[image:751.35.4.4.jpg|center|700px]]


:Replace U1 bars with V1 bars at piles between the girders.


:See [http://epg.modot.org/index.php?title=751.50_Standard_Detailing_Notes#G1._Concrete_Bents EPG 751.50 G1 Concrerte Bents] for appropriate notes to be placed with details.
===751.35.4.5 Coil Inserts and Tie Rods===


=== 751.35.4.3 Wing Reinforcement ===
Threaded rods (coil tie rods) installed in coil inserts (coil ties) that are cast into the ends of prestressed girders and beams are believed to provide some aid in resisting positive moment forces.


Prestressed I-girders shown in the following details, steel structures are similar.
Coil ties and rods shall be detailed on the plan sheets for prestressed girders and beams.


{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
<center>
{| border="1" class="wikitable" style="margin: 1em auto 1em auto" style="text-align:center"
|+
| style="background:#BEBEBE" width="300" |'''[http://www.modot.org/business/consultant_resources/bridgestandards.htm Bridge Standard Drawings]'''
|-
|-
|[[Image:751.35.4.3.jpg|850px]]
|align="center"|[https://www.modot.org/prestressed-i-girders-psi Prestressed I-Girders]
|-
|-
!valign="top"|Elevation of Wing||Part Section<br/>Thru Wing
|align="center"|[https://www.modot.org/prestressed-box-beams-psbxb Prestressed Box Beams]
|}
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|valign="top" align="right"|*||align="left" width="400pt" |Keep a min. of 3" ctr. to ctr. spacing between #6 bars placed horizontally and #8 bars placed with grade.
|-
|valign="top" align="right"|[[Image:751.35 circled 2.gif]]||align="left" width="400pt" |Use const. joint on steel structures only.
|}
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|[[Image:751.35.4.3 sections.jpg|800px]]
|-
|valign="top"|'''Section A-A (Squared)'''<br/>(K bars not shown for clarity)||'''Part Section Thru<br/>End of Wing'''
|}
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|valign="top" align="right"|[[Image:751.35 circled 1.gif]]||align="left" width="400pt" |Use 90° standard hook in seismic areas.
|}
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|[[Image:751.35.4.3 skewed.jpg|800px]]
|-
!Part Plan - Skewed End Bent
|}
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|Instructions:
|- 
|valign="top" align="right"|**||align="left" width="400pt" |See [http://epg.modot.org/index.php?title=751.50_Standard_Detailing_Notes#G1._Concrete_Bents EPG 751.50 G1 Concrete Bents] for note required for the #6-F bars.
|-
| ||align="left" width="400pt" |See [[751.12_Protective_Barricades#integral end bent barrier curb|EPG 751.12.2.3 End Bent Reinforcement]] for details of K bars at integral end bents.
|}
|}
</center>


===751.35.4.4 Skewed Bents===
Coil ties and coil tie rods shall be detailed on the plan sheets for integral end bents as shown below. Girders and beams with coil ties and rods are available as standard cells under the concrete diaphragm tasks in MicroStation.  
   
   
Prestressed I-girders shown in the following details, steel structures are similar.
[[image:751.35.4.5.jpg|center|650px]]
 
{| style="margin: 1em auto 1em auto"
The sections thru integral end bents previously shown shall be adjusted for skew as shown.  
 
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|-
|[[Image:751.35.4. sections.jpg|950px]]
| align="left|'''Detailing Guidance: '''
|-
|-
!Section Thru<br/>Squared End Bent<br/>(between piles and girders or beams)||Section Thru<br/>Skewed End Bent<br/>(between piles and girders or beams)
| align="left|<font color = "grass">Green items</font color = "grass"> are guidance and shall not be shown on plans.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 1.gif]]||align="left" width="400pt" |Use same as bottom reinforcement.
| align="left width="750"|Details shows I girders but are applicable for all girder and beams based on coil tie<br/>locations shown for closed diaphragms on the bridge standard drawings for prestressed<br/>girders and beams.
|-
|-
|valign="top" align="right"|[[Image:751.35 circled 2.gif]]||align="left" width="400pt" |Use construction joint on steel structures only.
|align="left width="750"|<font color = "grass">(a)</font color = "grass"> “Two” not required for bulb-tee and NU girders.
|-
|colspan="2"| &nbsp;
|-
|[[Image:751.35.4.4 plan.jpg|900px]]
|-
!Plan of<br/>Squared End Bent||Plan of<br/>Skewed End Bent
|}
|}


Line 601: Line 531:
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|+'''Reinforcing Holes for Wide Flange Beams'''
|+'''Reinforcing Holes for Wide Flange Beams'''
|[[Image:751.35 details-section at end of stringer.gif]]
|[[Image:751.35.5.1 end of stringer.jpg|450px]]
|[[Image:751.35 details-section a-a.gif]]
|[[Image:751.35 details-section a-a.gif]]
|-
|-
!Section at End of Stringer||Section A-A
!Section at End of Beam||Section A-A
|}
|}


Line 610: Line 540:
{|border="1" cellpadding="5" cellspacing="0" align="center" style="text-align:center"
{|border="1" cellpadding="5" cellspacing="0" align="center" style="text-align:center"
|-
|-
!WF Beam Depth||Stud Spacing||"A"||Reinforcing Hole Spacing
!WF Beam Depth||Stud Spacing||A||Reinforcing Hole Spacing
|-
|-
|21"||2 spa, @ 4/12"||4"||2 equal spaces
|21"||2 spa, @ 4 1/2"||4"||2 equal spaces
|-
|-
|24"||2 spa. @ 6"||4"||2 equal spaces
|24"||2 spa. @ 6"||4"||2 equal spaces
Line 631: Line 561:
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|+'''Reinforcing Holes for Plate Girders'''
|+'''Reinforcing Holes for Plate Girders'''
|colspan="2"|[[Image:751.35 details-section at end of girder.gif]]
|colspan="2"|[[Image:751.35.5.1 end of girder.jpg|600px]]
|-
|-
!width="45%"|Section at End of Girder|| &nbsp;
!width="45%"|Section at End of Girder|| &nbsp;
Line 637: Line 567:
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|-
|valign="top" align="right"|Note:||align="left" width="400pt" |Check the dead load (DL) on angles for girders 60" or larger.
|valign="top" align="right"|Note:||align="left" width="400pt" |Bearing stiffeners are to be designed for DC (no SBC or FWS) and 50 psf construction load.  (No web studs are required since bearing stiffener is provided).
|-
| &nbsp;||align="left" width="400pt"|Bearing stiffeners are to be designed for DL1 (no SBC or FWS) and 50 psf construction load.  (No web studs are required since bearing stiffener is provided).
|-
|-
|valign="top" align="right"|(***)||align="left" width="400pt"|1 1/16"&oslash; holes for skews thru 20°.  For skews > 20°, use slotted hole = 1 1/16" + 2(Web thickness)x(tan of the skew angle)
|valign="top" align="right"|***||align="left" width="400pt"|1 1/16"&oslash; holes for skews thru 20°.  For skews > 20°, use slotted hole = 1 1/16" + 2(Web thickness)x(tan of the skew angle)
|}
|}


Line 647: Line 575:
{|border="1" cellpadding="5" cellspacing="0" align="center" style="text-align:center"
{|border="1" cellpadding="5" cellspacing="0" align="center" style="text-align:center"
|-
|-
!PL Girder Depth||"A"||Reinforcing Hole Spacing
!PL Girder Depth||A||Reinforcing Hole Spacing
|-
|-
|39"||3 1/2"||4 equal spaces
|39"||3 1/2"||4 equal spaces
Line 662: Line 590:
=== 751.35.5.2 Vertical Drains ===
=== 751.35.5.2 Vertical Drains ===


{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
<center>
{| border="1" class="wikitable" style="margin: 1em auto 1em auto" style="text-align:center"
|+
| style="background:#BEBEBE" width="300" |'''[http://www.modot.org/business/consultant_resources/bridgestandards.htm Bridge Standard Drawings]'''
|-
|-
|colspan="2"|[[Image:751.35 vertical drains-elevation at end bent.gif]]
|align="center"|[http://www.modot.org/business/standard_drawings2/drains_new_title_block.htm Vertical Drain at End Bents]
|-
!colspan="2"|Elevation at End Bent
|-
|colspan="2"| &nbsp;
|-
|[[Image:751.35 vertical drains-section a-a.gif]]
|[[Image:751.35 vertical drains-detail b.gif]]
|-
!Section A-A||Detail "B"
|-
|colspan="2"| &nbsp;
|-
|[[Image:751.35 vertical drains-detail c.gif]]
|[[Image:751.35 vertical drains-elevation of wing.gif]]
|-
!Detail "C"||Elevation of Wing
|}
|}


</center>




{|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
|-
|[[Image:751.35 vertical drains-elevation of wing1.gif]]
|[[Image:751.35 vertical drains-part plan.gif]]
|-
!Elevation of Wing||Part Plan
|-
!colspan="2"|Optional Bent Drain (*)
|-
|colspan="2"|(*) Only if rock is encountered at outside of wings.
|}


[[Category:751 LRFD Bridge Design Guidelines]]
[[Category:751 LRFD Bridge Design Guidelines]]

Latest revision as of 13:19, 19 July 2024

751.35.1 General

751.35.1.1 Material Properties

Concrete
Class B Concrete (Substructure) = 3.0 ksi
  = 10

Class B-1 Concrete (Substructure) may also be used in special cases (See Project Manager). The following equations shall apply to both concrete classes:


Modulus of elasticity,

Where:

f'c in ksi
wc = unit weight of nonreinforced concrete = 0.145 kcf
K1 = correction factor for source of aggregate
= 1.0 unless determined by physical testing


Modulus of rupture,

      LRFD 5.4.2.6

Where:

f'c is in ksi


Reinforcing Steel
Minimum yield strength, = 60.0 ksi
Steel modulus of elasticity, = 29000 ksi

751.35.2 Design

751.35.2.1 Limit States and Factors

In general, each component shall satisfy the following equation:

Where:

= Total factored force effect
= Force effect
= Load modifier
= Load factor
= Resistance factor
= Nominal resistance
= Factored resistance


Limit States

The following limit states shall be considered for abutment design:

STRENGTH – I
STRENGTH – III
STRENGTH – IV
STRENGTH – V
SERVICE – I
FATIGUE
EXTREME EVENT - II

See LRFD Table 3.4.1-1 and LRFD 3.4.2 for Loads and Load Factors applied at each given limit state.


Resistance factors

STRENGTH limit states, see LRFD 5.5.4.2 and LRFD 6.5.4.2
For all other limit states, = 1.00


Load Modifiers

751.35.2.2 Loads

Dead Loads

Loads from beams, girders, etc. shall be applied as concentrated loads applied at the centerline of bearing. Loads from concrete slab spans shall be applied as uniformly distributed loads.


Live Loads

Loads from beams, girders, etc. shall be applied as concentrated loads applied at the centerline of bearing. Dynamic load allowance (impact) should be included for the design of the beam. No dynamic load allowance should be included for foundation design.

For wings with detached wing walls, no portion of the bridge live load shall be distributed to the detached wall. The detached wing wall shall be designed as a retaining wall. The weight of the barrier or railing on top of the wall shall be included in the dead load.

Collision

Collision shall be designed if abutments are located within a distance of 30.0 feet to the edge of roadway, or within a distance of 50.0 feet to the centerline of a railway track and conditions do not qualify for exemptions given in EPG 751.2.2.6.

751.35.2.3 General Design Assumptions

Beam

The beam shall be assumed continuous over supports at centerline of piles.

One half of the dead load of the approach slab shall be included in the beam design.


Wing

The standard horizontal reinforcement shown below was designed for soil pressure, EH, live load surcharge, LS and a railing collision force, CT for Extreme Limit State II Load Combination.



The minimum steel placed horizontally in wings shall be as shown in the figure below.


Part Section Thru Beam

751.35.2.4 End Bent Analysis

The following steps shall be used to design integral end bents.

751.35.2.4.1 Beam Cap Design

Step 1 – Obtain loads from superstructure

The live load reactions (LL), dead load of structural components (DC), and dead load of future wearing surface (DW) will be needed to design the end bents. Strength I Load Combination will be used to design the reinforcement.


Step 2 – Design bearing pads or girder chairs

From the loads obtained in Step 1, design the bearing pads or girder chairs according to EPG 751.11.


Step 3 – Find beam cap width

The standard beam cap width will be 3’-0”. However, if the bearing pad size required exceeds the allowable edge distance, the beam cap width may be widened. The bearing pads shall be centered over the centerline of pile location, which is 15” away from the stream or crossing face of the cap.


Step 4 – Design longitudinal steel in beam cap

If the centerline of bearing is 12” or less on the centerline of piles, use 4 - #6 bars at the top and bottom of the beam cap. Otherwise, the ultimate moment used for designing the longitudinal steel shall be approximated by the following equation and figure. The loads shall be factored according to the Strength I Load Combination.

Where:

= maximum interior girder reaction of factored superstructure loads, kips.
= pile spacing, ft.
= factored substructure loads equally distributed across the beam, k/ft.


Basic Assumption for Beam Analysis


A minimum of 4 - #6 Bars shall be used for the longitudinal steel in the beam cap. If more steel is required, increase bar size and keep the number of bars to 4. For example, use 4 - #7 bars instead of 5 - #6 bars.

The minimum reinforcement and bar spacing shall also be checked against the appropriate limits.

751.35.2.4.2 Pile Design

Follow Fig. 751.35.2.4.2 Integral Abutment Pile Design Flowchart and select applicable pile design method from following list:

1. Rigorous pile design procedure
2. Simple pile design procedure
3. Design pile in accordance with LRFD specification
Fig. 751.35.2.4.2 Integral Abutment Pile Design Flowchart
751.35.2.4.2.1 Rigorous Pile Design Procedure

See Development Section, Structural Project Manager (SPM), or Structural Liaison Engineer (SLE), or 17-01-SEP-New Integral End Bent Pile Design Procedure.

751.35.2.4.2.2 Simple Pile Design Procedure

Use this procedure if bridge meets the length and skew limits tabulized in Fig. 751.35.2.4.2, Integral Abutment Pile Design Flowchart, bridge does not require a complete seismic analysis and where scour can be ignored.

Simple curved structures following similar length and skew limits are allowed. Complex thermal movements may require rigorous procedure.

Minimum pile embedment, See EPG 751.1.2.22 Types of Piling.

Rotate HP piles for skews over 45°, resulting in strong axis parallel to center line of beam cap.

Show pile prebore elevation on the plan where applicable in accordance with flowchart. Side friction in prebored areas shall be ignored.

See EPG 751.36.5.7.1 Integral End Bent Simple Pile Design for typical pile design values.

751.35.2.5 Beam Reinforcement Special Cases

SPECIAL CASE I

If centerline bearing is 12" or less on either side of centerline piles, for all piles (as shown below), use 4-#6 top and bottom and #4 at 12" cts. (stirrups), regardless of pile size.


SPECIAL CASE II

When beam reinforcement is to be designed assuming piles to take equal force, design for negative moment in the beam over the interior piles.

(*) Dimensions are for illustration purposes only.

751.35.3 Dimensions

751.35.3.1 Front Sheet

Notes: The following are details and dimensions for the Plan view on the Front Sheets.
  Details for unsymmetrical roadways will require dimensions tying Centerline Lane to Centerline Structure.


751.35.3.2 Wing Brace

The wing brace dimensions will only vary on the wing with obtuse angle. Wing brace dimensions shown are minimum dimensions. The wing brace with the acute angle will always be 18" minimum.

Skews 0° thru 45°
 
Skews 45°00'01" thru 55°
 
Skews 55°00'01" and Over
Note: Left advance shown, right advance similar.

751.35.3.3 Prestressed Girder End Bent

(1) See EPG 751.12 Barriers, Railings, Curbs and Fences for barrier or railing details.
(2) Keep 1 1/2" minimum clear cover for reinforcement between approach notch and girder. Increase beam width (1" increments) to get the 1 1/2" clear cover if necessary.
(3) Use 1” plus half of bearing pad length when bearing pads are used. Use 3 ½” minimum for NU Standard Girders and 5” minimum for MoDOT Standard Girders when girder chairs are used.
(4) 12" minimum at gutter line at end of slab.
(5) All concrete in the end bent above top of beam and below top of slab shall be Class B-2.
(6) Provide a minimum of 8" clearance from outside edge of pile to face of beam. For pile greater than 14” wide (diameter), shifting pile centerline towards fill face is preferred based on structural considerations (eccentric load to pile). Otherwise, increase beam width (1” increments) toward front face in order to meet 8” minimum clearance.
Example:
Pile size = 16”
Option I (preferred): Shift pile centerline 1” toward fill face and consider eccentric load to the pile.
Minimum beam width = 20”+16”=3’-0”
Option II: Increase beam width 1” toward front face.
Minimum beam width = 21”+16”=3’-1”
(7) See Design Layout for maximum spill slope.


Note: Neoprene bearing pads are to be used on integral bents (prestressed structures) if pad size and beam clearance permit; otherwise, use girder chairs. See EPG 751.11.3.6 Girder/Beam Chairs for additional girder chair details.
Squared beam steps are shown. Steps may be skewed to facilitate placement of U1 and V1 stirrup bars. See EPG 751.35.4 Reinforcement for details.
* 18" minimum, 2'-0" maximum; provide a minimum of 8" clearance from outside edge of pile to outside face of beam.

751.35.3.4 Steel Girder or Beam End Bent

(1) See EPG 751.12 Barriers, Railings, Curbs and Fences for barrier or railing details.
(2) Keep 1 1/2" minimum clear cover for reinforcement between approach notch and girder. Increase abutment beam width (1" increments) to get the 1 1/2" clear cover if necessary.
(3) Use 1" plus half of bearing pad length when bearing pads are used. Use 3" minimum when girder chairs are used.
(4) 12" minimum at gutter line at end of slab.
(5) All concrete in the end bent above top of beam and below top of slab shall be Class B-2.
(6) Provide a minimum of 8" clearance from outside edge of pile to face of beam. For pile greater than 14” wide (diameter), shifting pile centerline toward fill face is preferred based on structural considerations (eccentric load to pile). Otherwise, increase beam width (1” increments) toward front face in order to meet 8” minimum clearance.
Example:
Pile size = 16”
Option I (preferred): Shift pile centerline 1” toward fill face and consider eccentric load to the pile.
Minimum beam width = 20”+16”=3’-0”
Option II: Increase beam width 1” toward front face.
Minimum beam width = 21”+16”=3’-1”
(7) See Design Layout for maximum spill slope.


Note: Neoprene bearing pads are to be used on integral bents (steel structures) if pad size and beam clearance permit; otherwise, use girder chairs. See EPG 751.11.3.6 Girder/Beam Chairs for additional girder chair details.
Squared beam steps are shown. Steps may be skewed to facilitate placement of U1 and V1 stirrup bars See EPG 751.35.4 Reinforcement for details.
* 18" minimum, 2'-0" maximum; provide a minimum of 8" clearance from outside edge of pile to outside face of beam.
** 3" minimum clearance between sole plate and keyed construction joint (typical)

751.35.3.5 Wing and Detached Wing Walls

For seismic design category A: When wing length, L, is greater than 22’-0”, use maximum 22’-0” integral abutment wing wall combined with detached wing wall.

Standard wing reinforcement is developed assuming a pinned connection at the bottom (tip) of wing. This assumption is applicable for cases where the passive pressure from the fill slope can be counted on to partially resist the active forces from the backfill. In a seismic event the forces on the wings are developed by the wings moving into the soil backfill and the fill slope resistance is less reliable. For seismic forces wings shall be designed assuming there is no lateral restraint at the bottom of the wing. The reduced restraint conditions require a more practical limit for the wing length.

Note:
* Detached wing wall shown is for illustration purpose only. Design detached wing wall as a retaining wall (EPG 751.24).
** Use retaining wall design.
1 For seismic design category B, C and D only: The wing length shall not be greater than 17 feet. When a detached wing wall is required the integral abutment wing length shall not exceed 17 feet.
Report Pile Cut-off Elevation and Minimum Galvanized Penetration (Elev.) (See EPG 751.50 Standard Detailing Note E2, (Foundation Data Table).

751.35.4 Reinforcement

For epoxy coated reinforcement requirements, see EPG 751.5.9.2.2 Epoxy Coated Reinforcement Requirements.

751.35.4.1 Wide Flange Beams & Plate Girders

Detailing Guidance:
ko Green items are guidance only and shall not be shown plans.
Place all U bars and V pairs parallel to centerline roadway.
Keep 1 1/2" clearance between the piles and the U1 or U2 bars.
Keep 1 1/2" clearance between the beams or girders and the U1 or V1 bars.
Keep 1 1/2" clearance between the angles of girder chairs and the U2 or U3 bars.
Replace U1 bars with U3 bars at piles under beams or girders.
Replace U1 bars with V1 bars at piles between beams or girders.
When dimension “A” is required to be greater than 15” to clear piles by 1 ½”, typical when HP14 and CIP14 or larger diameter piles are used, add intermediate longitudinal bar(s) between piles. The spacing between intermediate bar(s) and full length bars shall not be greater than required by crack control provisions. Ends of intermediate bar(s) shall be hooked.
See EPG 751.50 G1 Concrete Bents for appropriate notes to be placed with details.
(1) #6-U bar () at 9" centers between barrier curbs. For shallow beams where 26” is not available extend to top of beam minus 1” clear.
(2) U4 bars () and #6-U5 bars () spliced with U1 () and V1 bars (│). U4 bars shall be same size as U1 bars. Show lap splice on plans as shown. For shallow beams stirrup hooks may be required for U4 bars ( -Shape 37S) (see Alternate Sections). For shallow beams where 16” is not available extend stirrup hooks to top of beam minus 1” clear.
(3) U1 bars () at 12" centers. Typically #5 bars, except special cases. Replace with pairs of #5-V1 bars (│) at piles. Make sure U1 and V1 bars extend enough to meet lap length requirement across length of diaphragm. For shallow beams stirrup hooks may be required for U1 bars ( -Shape 37S) and end hooks may be required for V1 bars () (see alternate sections). For shallow beams where 16” is not available extend hooks to approach notch minus 1 1/2" clear.
(4) Stirrups shall clear step by 1 1/2" minimum, if not lengthen step or skew step.
(5) #6-V bars at no more than 9” centers at the end of girders or beams.
(6) #5-U bars (15”H x 24”V) @ about 12" centers placed parallel to centerline roadway. When approach slab haunch is expected to be greater than 18” at the roadway crown at the end of slab, slope the approach slab notch providing 12” of constant approach slab haunch or with SPM or SLE approval greater than 18” approach slab haunch may be used but increase vertical leg length of #5-U bars to ensure 12” minimum embedment.
For shallow beams where 12” embedment is not available adjust length of vertical leg and extend to top of beam minus 1” clear.
(7) With SPM or SLE approval a 29” splice may be used in combination with specifying 2” cover to U bars and V bars if doing so avoids the need for using hooked bars.
(8) See tables for 1 1/16" round hole spacing for #6-H bars.
(9) Same number of bars as 1 1/16" round holes in beam or girder.
(10) Add intermediate longitudinal bar(s) when required for spacing. Keep 3” minimum clearance between the pile and intermediate longitudinal bar(s).

751.35.4.2 Prestressed I-Girders, Bulb-Tee Girders and NU-Girders

Detailing Guidance:
ko Green items are guidance only and shall not be shown on plans.
Place all U bars and V pairs parallel to centerline roadway.
Keep 1 1/2" clearance between the piles and the U1 or U2 bars.
Keep 1 1/2" clearance between the beams or girders and the U1 or V1 bars.
Keep 1 1/2" clearance between the angles of girder chairs and the U2 or U3 bars.
Replace U1 bars with U3 bars at piles under beams or girders.
Replace U1 bars with V1 bars at piles between beams or girders.
When dimension “A” is required to be greater than 15” to clear piles by 1 ½”, typical when HP14 and CIP14 or larger diameter piles are used, add intermediate longitudinal bar(s) between piles. The spacing between intermediate bar(s) and full length bars shall not be greater than required by crack control provisions. Ends of intermediate bar(s) shall be hooked.
See EPG 751.50 G1 Concrete Bents for appropriate notes to be placed with details.
(1) #6-U bar () at 9" centers between barrier curbs. For shallow beams where 26” is not available extend to top of beam minus 1” clear.
(2) U4 bars () and #6-U5 bars () spliced with U1 () and V1 bars (│). U4 bars shall be same size as U1 bars. Show lap splice on plans as shown. For shallow beams stirrup hooks may be required for U4 bars ( -Shape 37S) (see Alternate Sections). For shallow beams where 16” is not available extend stirrup hooks to top of beam minus 1” clear.
(3) U1 bars () at 12" centers. Typically #5 bars, except special cases. Replace with pairs of #5-V1 bars (│) at piles. Make sure U1 and V1 bars extend enough to meet lap length requirement across length of diaphragm. For shallow beams stirrup hooks may be required for U1 bars ( -Shape 37S) and end hooks may be required for V1 bars () (see alternate sections). For shallow beams where 16” is not available extend hooks to approach notch minus 1 1/2" clear.
(4) Stirrups shall clear step by 1 1/2" minimum, if not lengthen step or skew step.
(5) #6-V bars at no more than 9” centers at the end of girders or beams.
(6) #5-U bars (15”H x 24”V) @ about 12" centers placed parallel to centerline roadway. When approach slab haunch is expected to be greater than 18” at the roadway crown at the end of slab, slope the approach slab notch providing 12” of constant approach slab haunch or with SPM or SLE approval greater than 18” approach slab haunch may be used but increase vertical leg length of #5-U bars to ensure 12” minimum embedment.
For shallow beams where 12” embedment is not available adjust length of vertical leg and extend to top of beam minus 1” clear.
(7) With SPM or SLE approval a 29” splice may be used in combination with specifying 2” cover to U bars and V bars if doing so avoids the need for using hooked bars.
(8) Add intermediate longitudinal bar(s) when required for spacing. Keep 3” minimum clearance between the pile and intermediate longitudinal bar(s).

751.35.4.3 Wing Reinforcement

Detailing Guidance:
Green items are guidance only and shall not be shown on plans.
Bar marks shown are for these details only. Vary as needed.
K bars not shown in the Elevation of Wing for clarity. For details of K bars, see EPG 751.12.1.4.3 End of Barrier Reinforcement for Type B barrier and EPG 751.12.1.3.3 End of Barrier Reinforcement for Type D and H barriers.
See EPG 751.35.3.3 for chamfer detail.
(a) Use dimension that provides a minimum of 3" center to center spacing between #6 bars placed horizontally and #8 bars placed with grade. See SPM or SLE if spacing at one end exceeds 8 inches due to grade.
(b) Use construction joint on steel structures only.
(c) 6 3/8” min and 11 3/8” max. If unable to get dimension to fall within this range using 8-inch centers, then use 6 3/8” and use “@ abt. 8” cts.”
(d) Use 66.5” for obtuse corner of bents skewed 55 degrees or greater.
(e) Use 54.5” for obtuse corner of bents skewed 55 degrees or greater.
(f) See EPG 751.50 G1 Concrete Bents for note required for the #6-F bars.
(g) Use 90 degree standard hook in seismic areas.

751.35.4.4 Skewed Bents

Prestressed I-girders shown in the following details, steel structures are similar.

The sections thru integral end bents previously shown shall be adjusted for skew as shown.


751.35.4.5 Coil Inserts and Tie Rods

Threaded rods (coil tie rods) installed in coil inserts (coil ties) that are cast into the ends of prestressed girders and beams are believed to provide some aid in resisting positive moment forces.

Coil ties and rods shall be detailed on the plan sheets for prestressed girders and beams.

Bridge Standard Drawings
Prestressed I-Girders
Prestressed Box Beams

Coil ties and coil tie rods shall be detailed on the plan sheets for integral end bents as shown below. Girders and beams with coil ties and rods are available as standard cells under the concrete diaphragm tasks in MicroStation.

Detailing Guidance:
Green items are guidance and shall not be shown on plans.
Details shows I girders but are applicable for all girder and beams based on coil tie
locations shown for closed diaphragms on the bridge standard drawings for prestressed
girders and beams.
(a) “Two” not required for bulb-tee and NU girders.

751.35.5 Details

751.35.5.1 Reinforcing Holes

Reinforcing Holes for Wide Flange Beams
Section at End of Beam Section A-A


WF Beam Depth Stud Spacing A Reinforcing Hole Spacing
21" 2 spa, @ 4 1/2" 4" 2 equal spaces
24" 2 spa. @ 6" 4" 2 equal spaces
27" 2 spa. @ 7 1/2" 4 1/2" 2 equal spaces
30" 3 spa. @ 6" 4 1/2" 3 equal spaces
33" 3 spa. @ 7" 4 1/2" 3 equal spaces
36" 4 spa. @ 6" 4 1/2" 3 equal spaces



Reinforcing Holes for Plate Girders
Section at End of Girder  
Note: Bearing stiffeners are to be designed for DC (no SBC or FWS) and 50 psf construction load. (No web studs are required since bearing stiffener is provided).
*** 1 1/16"ø holes for skews thru 20°. For skews > 20°, use slotted hole = 1 1/16" + 2(Web thickness)x(tan of the skew angle)


PL Girder Depth A Reinforcing Hole Spacing
39" 3 1/2" 4 equal spaces
42" 3 1/2" 5 equal spaces
48" 4" 5 equal spaces
54" 4 1/2" 6 equal spaces
60" 4" 8 equal spaces

751.35.5.2 Vertical Drains

Bridge Standard Drawings
Vertical Drain at End Bents